HR7 High Frequency Rectifier

Standard Features

hr
  • SCR design for Maximum reliability
  • Negligible input harmonics
  • Hi / Low Voltage Alarm (Rectifier Failure)
  • AC Fail with indication and Form C relay
  • Automatic Equalize after discharge
  • AC Breaker 2 Pole for Single phase, 3 Pole for 3 Phase
  • DC Breaker 2 Pole
  • 5” HMI for display and entering control parameters
  • MTBF 100,000 Hours
  • Communication : Ether-Net, Profibus, Device Net, Control Net Mod Bus TCP/IP.

Specification

Regulation: < 0.5% for input variation of 10%
Short Circuit Protection: Electronic SCP
Enclosure: NEMA 1
Efficiency: > 90%
Power Factor: >0.85
Soft start: Electronic soft start
Ripple: 4% (2%, 1% optional)
Operation:
0-50 Degree Celsius
(-40 Degree Operation Optional)
Operation Mode: Constant Current with adjustable Voltage limit
Cooling: Natural Convection, Forced air (High Power), Vortex cooling Optional
Cabinet: Wall mount, Floor mount Rating dependant (Stainless Steel Optional)

Input / Output / Approval

Input Voltage: 120, 220, 380, 480, 575, 690, Custom 1 / 3 Phase 50/60 Hz
Output Voltage: 12, 24, 48, 125, 250, 600, Custom
Output Current: Up to 2500A
Approvals: CSA, CSA us (UL)

pdf format HR7 Brochure (PDF 116 KB)